3
D 215 - RTR 684 C2 Eng. 14.06.00
We reserve the right to make changes without notice
COSTER
B1 – Primary t° detector (0 ... 99 °C)
B2 – Primary flow limit t° detector
B3 – Primary t° detector (0 ... 40 °C)
B4 – Boiler anticondensing t° detector
B5 – Auxiliary t° detector
7. WIRING DIAGRAM
R – Remote control for modifying programmes
Rt° – Primary temperature set point adjuster
M1 – Primary circuit pump
M2 – Auxiliary circuit pump
Y1 – Primary control valve
8. SITING CONTROLLER
The controller must be sited in a dry space which meets the relevant ambiental limits shown under 4. TECHNICAL
DATA. If sited in a space classified as “Dangerous” it must be installed in a cabinet for electrical devices
constructed according to the regulations in force for the danger class involved.
The controller can be installed on a DIN rail or in a DIN modular enclosure.
9. WIRING
Proceed as follows:
• Separate base and cover
• Mount base on DIN rail and check that securing elements (5.4) hold it firmly in place.
• Carry out wiring according to the diagram and in observance of the regulations in force, using cables of :
– 1.5 mm
2
for power and relay control outputs
– 1 mm
2
for detectors and remote control
– 1 mm
2
for C-Ring. For limits of cable length please see technical data sheet T 022
• Switch on power (230 V ~) and check voltage across terminals L and N
• Switch off power, replace cover on base and secure it with the four screws supplied (5.3).
You are advised not to insert more than two cables in a single terminal of the controller and if necessary to use
external junction boxes.
Y1
1
Co
3
Cl
2
Op
B2B1 B4
T
B5
Rt°
N
230 V ~
L
0
D UE
M
B5
B4
MB3
B2
MB1
11 12 13
14
RTR 684
C RING
B6
5 6 7 L L N N 8 9 10
R
M2
NL
M1
NL
T T
B3
T
1 2
3
4
E1 E2 E3
B7
34
T