4. TECHNICAL DATA
• Electrical
Power supply 230 V~ ± 10%
Frequency 50…60 Hz
Consumtion 5 VA
Protection IP40
Radio disturbances VDE0875/0871
Vibration test with 2g(DIN 40 046)
Voltage-free output contacts:
maximum switching voltage 250 V ~
maximum switching current 5 (1) A
Construction standards Italian Electrotech. Committee (CEI)
Storage data in memory 5 years
• Mechanical
Case DIN 6E module
Mounting DIN 35 rail
Materials:
operating NYLON
storage ABS
Ambient temperature:
operating 0…45 °C
storage – 25…+ 60 °C
Ambient temperature Class F DIN 40040
Dimensions 105 x 115 x 71.5
Weight 1.0 kg
• Measurement ranges
Primary temperature 0…99 °C or 0…40 °C
Limit temperature (min. and max.) 0…99 °C
Anticondensig temperature 0…99 °C
Auxiliary temperature 0…99 °C
• Setting ranges : primary control
Desired temperatures :
with detector B1 0…99 °C
with detector B3 0…40 °C
5. OVERALL DIMENSIONS 6. FACIA
1 – Backlighted two-line alphanumeric display
2 – + and – operating keys
3– and operating keys
4 – LEDs for Opens-Closes primary valve or 1
st
and 2
nd
stage
5 – Primary pump LED
6 – Auxiliary pump LED
7 – Real time clock alarm LED
8 – C-Ring alarm LED
9 – Fault LED
1 – Protective cover for electronic components
2 – Base with transformer, relay & terminal blocks
3 – Screws for fixing cover and base
4 – DIN rail securing elements
5 – DIN rail release lever
1
2
3
3
4
5
Adjuster desired temperature:
with detector B1 (0 … 40 °C) ± 5 °C
with detector B3 (0 … 99 °C) ± 10 °C
Limit temperature detector 1…99 °C
Anticondensing temperature 10…50…99 °C
24-hour programmes 1…4
7-day programmes 0…1
Delay switching off pump 0…60 min
Control output : 3-wire modulating
– On-Off (1 or 2 stages)
Modulating :
actuator run time 30…630…1,800 sec.
proportional band 0.5…10…50 °C
integral time 0,5…10…99,5 min.
On-Off :
On-Off differential 0.5…10…50 °C
minimum start time 0…60…990 sec.
minimum stop time 0…60…990 sec.
• Setting ranges : auxiliary control
Desired temperature 0…20…99 °C
24-hour programmes 1…3
7-day programmes 0…1
Delay switching off heating pump 0…60 min
Control output : On-Off differential
– On-Off proportional
Data output On-Off differential :
differential 0.5…10…50 °C
minimum start time 0…60…990 sec.
minimum stop time 0…60…990 sec.
Data output On-Off proportional :
proportional band 0.5…10…50 °C
integral time 0,5…10…99,5 min.
half-cycle time 60…120…990 sec.
In presence of electrical disturbances the output controls of
controller may change status but this will be restored
automatically.
TEMPERATURE
CONTROLLER
RTR 684
COSTER
PRIMARY
+
!
ALARMS
AUX
C RING
6 754 8 9 3
2
1
105
115
35
50.5 21
45
Vista de página 1