D 215 - RTR 684 C2 Eng. 14.06.00
We reserve the right to make changes without notice
COSTER
14.3 Auxiliary control priority function
Auxiliary zone priority
:NO
= function disabled
YES
= function enabled
When RTR 684 is connected in C-Ring with other controllers and the priority function has been
enabled :
– auxiliary control sends via C-Ring the differential value between its own desired temperature
and the actual one ;
– the controllers in C-Ring, with the anticondensing function enabled, decrease their own desired
flow temp. by 4 °C for each °C of difference so as to give precedence to the auxiliary control of
RTR 684.
Note When the priority function is used and the boiler asks for the presence of the anticondensing
detector it is indispensable to connect it to the first RTR 684 controller in the C-Ring.
Auxiliary zone
priori ty : NO
23.6
15. PROGRAMMES
There are separate programmes of timed events for primary control and for auxiliary control.
15.1 24-hour programmes
Set the number of 24-hour programmes you wish to use for the primary zone (1 ... 4) and for the
auxiliary zone (1 ... 3) so as to avoid scrolling unnecessary pages.
In each 24-hour programme you can set a maximum of six event start times (h1 ... h6) assigning to
each one of following modes :
for
primary
zone :
TEMP 1…5
: control with Desired Pri temp 1 ... 5 set in
OFF
: plant Off, valve closed and pump idle
for
auxiliary
zone :
ON
: control with Desired Aux temp set in
OFF
: plant Off, valve closed and pump idle
The event start times must be entered in increasing order.
Events not used must be excluded by pressing + and – keys at the same time.
Unused events must not be left between programmed events.
15.2 7-day programmes
Set the number of 7-day programmes you wish to use for the primary zone (0 ... 1) and for the
auxiliary zone (0 ... 1) so as to avoid scrolling unnecessary display pages.
In each 7-day programme you can assign to each day of the week one of following programmes :
primary
control :
24 HOUR 1 …4 PRI
;
TEMP1…5
;
OFF
.
for
auxiliary
control :
24 HOUR 1 …3 AUX
;
ON
;
OFF
.
15.3 BST period
The controller is able to change automatically the time according to the time period (GMT or BST) in
force.
Fr - -.- -
= the night of the last Saturday in March the clock is put forward automatically one
hour.
to - -.- -
= the night of the last Saturday in October the clock is put back automatically one
hour.
To cancel the period keep pressed + and – keys at the same time.
21.2 - 21.7
P1 Event 1 6 . 00
TEMP 3 21 . 0c
21.1 - 21.8
––– -Number 24hr
programmes ? 1
21.15 - 21.23
––– Number 7day
programmes ? 1
Des i r ed Aux
temp 20.0c
20.6
Desired Primary
temp 20.0c
20.1 - 20.5
21.9 - 21.14
P1 Event 1 6 . 00
ON 50 . 0 c
21.24 - 21.30
7day 1 :MONDAY
24HOUR 1 AUX
21.16 - 21.22
7day 1 :MONDAY
24HOUR 1 PR IMARY
21.31
BST pe r i od
Fr --.--to --.--