17
D 215 - RTR 684 C2 Eng. 14.06.00
We reserve the right to make changes without notice
COSTER
22. SETTING PRIMARY ZONE
Ref. Display Description Notes Sect.
Setpoint ad j us t
min l imi t :– 0 .0c
22.18
Mimimum limit of variation permitted to set point adjuster
Rt°. With B1 : 0…– 10 °C; with B3 : 0…– 5 °C.
13.5Appears only if in 24.1 set point adjuster Rt° has
been configured
Setpoint ad j us t
max l imi t : + 0 . 0c
22.19
Maximum limit of variation permitted to set point adjuster
Rt°. With B1 : 0…+ 10 °C; with B3 : 0…+ 5 °C.
13.5Appears only if in 24.1 set point adjuster Rt° has
been configured
An t i condens : NO
Desired T: 50.0c
22.20
Anticondensing function :
YES
;
NO
.
Value of desired boiler anticondensing temp.
16.1If in 24.1 detector B4 not configured & value comes
via C-Ring – – – will appear.
Pr imary zone
priori ty : NO
22.21
Priority function of primary zone :
YES
;
NO
.
13.7
P r i pump : AUT
De l ay Of f : 0m
22.22 Control of plant pump :
MAN
;
AUT
.
Delay in switching off pump.
13.8
MAN
: always On;
AUT
: On according to current programme of timed
events.
23. SETTING AUXILIARY ZONE
Rif. Display Description Notes Sect.
Con t r o l :ON-OFF
D I FFERENTIAL
23.1
Choice type On-Off control :
DIFFERENTIAL
;
PROPORTIONAL
DIFFERENTIAL
: with pure differential.
PROPORTIONAL
: with Proportional control action
(ambient).
14.
Di f f :10.0c
23.2
On-Off temperature differential 14.
Appears if in 23.1
DIFFERENTIAL
entered
.
Hal f cyc le t ime
120sec
23.3
Time of half cycle at half load : this is time of On or
Off when actual temp. is equal to desired temp.
14.
Appears if in 23.1 è
PROPORTIONAL
entered
.
Minimum star t
time : 60s
23.4
Minimum start time for On-Off control. 14.1
Miminimum stop
time: 60s
23.5
Minimum stop time for On-Off control. 14.1
Auxiliary zone
priori ty : NO
23.6 Priority function of auxiliary control :
YES
;
NO
. 14.3
Auxiliary pump
Delay Off: 0min
23.7
Delay in switching off auxiliary zone pump 14.1
Prop band : 10 . 0c
Integ time: 10m
Proportional band in ± °C.
Integral time in minutes
14.Appears if in 23.1 è
PROPORTIONAL
entered
.
Prop band : 10 . 0c
Integ time: 10m
22.13
Proportional band in ± ° C of primary temperature.
Integral time of primary temperature.
13.2
Flow temp
Di f f :10.0c
22.14
Flow temperature differential. 13.2
Con t r o l f l ow
Min: 1c Max:99c
22.15
13.2Minimum & maximum flow temp. limits.
Establish range of Proportional band of primary tem-
perature (22.13).
Minimum star t
time : 60s
22.16
Minimum start time for On-Off control. 13.3
Minimum stop
time : 60s
22.17
Minimum stop time for On-Off control. 13.3
22.23
Name Pr i zone
----------
16.3Entering name primary zone. Use + and – to enter letters or numbers.
Use ← and → to position cursor.
23.8
Name Aux zone
----------
16.3Entering name auxiliary zone. Use + and – to enter letters or numbers.
Use ← and → to position cursor.
Pages 22.13, 22.14, 22.15, 22.16,and 22.17 appear if detector B2 connected and if in 22.1
ON-OFF DIFF
entered
.