D 215 - RTR 684 C2 Eng. 14.06.00
We reserve the right to make changes without notice
COSTER
21. EVENTS & PERIODS
Ref. Display Description Notes Sect.
7day 1 :MONDAY
24HOUR 1 PR IMARY
7da y 1 : SUNDAY
24HOUR 1 PR IMARY
21.16
21.22
Choice of programme for each day of week :
24HOUR 1…4 PRI ; TEMP 1…5 ; OFF
.
15.2
BST pe r i od
Fr:29.03to:26.10
21.31 Dates of start and end of BST period. 15.3
Pr i Number 7day
programmes ? 1
21.15
Choice of number of 7-day programmes to be used
(0 ... 1) for primary zone.
Avoids scrolling unnecessary display pages 15.2
7day 1 :MONDAY
24HOUR 1 AUX
7da y 1 : SUNDAY
24HOUR 1 AUX
21.24
21.30
Choice of programme for each day of week :
24HOUR 1…3 AUX ; ON ; OFF
.
15.2
Aux Numbe r 7day
programmes ? 1
21.23 Choice of number of 7-day programmes to be
used (0 ... 1) for auxiliary zone.
Avoids scrolling unnecessary display pages 15.2
22. SETTING PRIMARY ZONE
Ref. Display Description Notes Sect.
Con t r o l :
MODULAT I NG
22.1
Choice of type of control
MODULATING
;
ON-OFF DIFF
MODULATING
: three-wire modulating control.
ON-OFF DIFF
: On-Off control in two stages
13.1.2.3
Prop band : 10 . 0c
Integ time: 10m
22.9 Proportional band in ± °C of primary temperature.
Integral time of primary temperature.
13.2
Ac t ua tor run t ime
630sec
22.2
Valve actuator run time in seconds. 13.3
Prop band : 10 . 0c
Integ time: 10m
22.3 Proportional band in ± °C.
Integral time in minutes.
13.1
Dead band
NARROW
22.4
Dead band of modulating output :
NARROW
;
MEDIUM
;
WIDE
.
13.3
Di f f :10.0c
Int eg t ime : 10m
Temperature differential On-Off per stage.
Integral time in minutes.
13.122.5
Minimum star t
time : 60s
22.6
Minimum start time for On-Off control. 13.3
Minimum stop
t ime: 60s
22.7
Minimum stop time for On-Off control. 13.3
Ac t ua tor run t ime
630sec
22.8 Valve actuator run time in seconds. 13.3
Flow temp
Prop band : 10 . 0c
22.10
Proportional band of flow temperature. 13.2
Con t r o l f l ow
Min: 1c Max:99c
22.11
Minimum & maximum limits of flow temperature.
Establish range of Proportional band for primary
temperature (22.9).
13.2
Dead band
NARROW
22.12
Dead band of modulating output :
NARROW
;
MEDIUM
;
LARGE
.
13.3
Pr i Number 24hr
programmes ? 1
21.1
Choice of number of 24-hour programmes
to be used (1 ... 4) for primary zone
Avoids scrolling unnecessary display pages. 15.1
P1 Event 1 6 . 00
ON
P1 Event 2 22 . 00
OFF
21.9
21.14
Number of programme, number of event and
start time programmed.
Choice type of mode to assign to period :
ON ; OFF
.
Further groups of 6 pages according to figure
entered in 21.1
Max 6 periods. To eliminate an unused period press
+ and - together : - - . - - will appear
The events must be in increasing order. Do not leave
- - . - - between programmed events.
Modes set are winter ones.
15.1
Aux Numbe r 24h r
programmes ? 1
21.8
Choice number of 24-hour programmes to be
used (1 ... 3) for auxiliary zone.
Avoids scrolling unnecessary display pages 15.1
Pages 22.2, 22.3, and 22.4 appear if detector B2 is not connected and if in 22.1
MODULATING
entered.
Pages 22.5, 22.6 and 22.7 appear if detector B2 is not connected and if in 22.1
ON-OFF DIFF
entered
.
Pages 22.8, 22.9, 22.10, 22.11 and 22.12 appear if detector B2 connected and if in 22.1
MODULATING
entered
.
P1 Event 1 6 . 00
TEMP 3 21 . 0c
P1 Event 2 22 . 00
OFF
21.2
21.7
Number of programme, number of event and
start time programmed. Choice type of mode to
assign to period :
TEMP 1…5 ; OFF
.
Further groups of 6 pages according to figure
entered in 21.1
Max 6 periods. To eliminate an unused period press
+ and – together : - - . - - will appear.
Events must be in increasing order. Do not leave
- - . - - between programmed events.
Modes set are winter ones.
15.1