16. COMPLEMENTARY FUNCTIONS
16.1 Control of boiler anticondensing temperature
The anticondensing function prevents the formation of condensation in the boiler combustion
chamber. It imposes a decrease of 4 °C in the desired flow temperature for each °C decrease in the
actual return to boiler temperature (detector B4) in respect of the value set, thereby bringing about
the progressive closure of the regulating valve.
•
Anticondens : NO
= function disabled
YES
= function enabled
•
Desired T : - - .-
°
C
= minimum limit value of return to boiler temperature
If controller is in C-Ring the differential value is transmitted to all the controllers connected, so that
these are able to perform the anticondensing function with a single detector. The value of the
desired anticondensing temp. is that set on the controller to which the anticondensing detector is
connected.
16.
2 Access keynumber
To enable the access keynumber enter the number (1900 ... 1999) using + and – keys.
The keynumber prevents use of + and - keys for changing data.
To cancel keynumber, press + and – at the same time until the dashes reappear.
When keynumber is enabled if + and – keys pressed on display appears
Only after having entered the exact keynumber can + and – keys be used.
If for 15 minutes no key is pressed the keynumber is automatically re-enabled.
16.3 Denomination zones
Entering names of primary and auxiliary zones which appear on relative pages of of programme
choices.
Using + and – keys, each dash can be replaced by a letter of the alphabet (A ... Z) or by a number
(0…9). The → key serves to position the cursor.
16.4 Display measurements
The controller displays all the measurements made by the detectors and the data useful for monitoring
the operational status of the zones.
• temperature
desired
by current mode for primary control.
•
actual
temperature measured by detector B1 or B3.
Appears only if detector B2 is connected and configured.
• flow temperature
desired
by primary control.
•
actual
flow temperature measured by detector B2.
Appears only if detector B5 is connected and configured.
• temperature
desired
by current mode for auxiliary control.
•
actual
temperature measured by detector B5.
Appears only if detector B4 is connected and configured.
•
desired
anticondensing temperature.
•
actual
temperature measured by detector B4.
16.
5 Alarms
The controller is able to indicate, by means of the three LEDs situated on the facia, certain operational
disfunctions :
– fault in internal real time clock (LED 6.7)
– fault in C-Ring (led 6.
8)
– fault in microprocessor (LED 6.
9)
An t i condens : NO
Desired T: 50.0c
22.20
24.3
Choice keynumber
----
Access keynumber
----
22.23
Name Pr i zone
----------
23.8
Name Aux zone
----------
19.8
Des Pr i T : 20 . 0c
Ac t Pr i T : 20 . 0c
19.9
Des f l ow T : 20 . 0c
Ac t f l ow T : 20 . 0c
19.10
Des Aux T : 20 . 0c
Ac t Aux T : 20 . 0c
19.11
Des ant icT:20.0c
Act ant icT:20.0c